<div class="csl-bib-body">
<div class="csl-entry">Heimberger, M. (2016). <i>Energy storage - optimisation of the placement and operation (in a distribution grid)</i> [Dissertation, Technische Universität Wien]. reposiTUm. https://doi.org/10.34726/hss.2016.28889</div>
</div>
-
dc.identifier.uri
https://doi.org/10.34726/hss.2016.28889
-
dc.identifier.uri
http://hdl.handle.net/20.500.12708/3556
-
dc.description
Zusammenfassung in deutscher Sprache
-
dc.description
Titelübersetzung des Autors: Energiespeicher - Optimierung der Platzierung und des Betriebes
-
dc.description.abstract
Die starke Integration von volatilen, erneuerbaren, dezentralen Erzeugungsanlagen in das Stromnetz, kann das elektrische System an seine Grenzen bringen. Durch Kopplung vorhandener Infrastrukturen (Strom-, Gas-, Fernwärmenetz) kann einerseits eine Entlastung des Stromsystems erreicht werden. Andererseits kann eine Reduktion des Primärenergiebedarfs für den Strom- und Wärmebedarf ermöglicht werden. Zusätzlich stellen Speicher ein probates Mittel zum Energie- und Leistungsausgleich zwischen volatiler, erneuerbarer Erzeugung und dem Verbrauch dar. Diese beiden Ansätze sollen in einer Modellregion, die die österreichischen Gebäude-, Wohnverhältnisse und Energieinfrastrukturmerkmale abbildet, untersucht werden. Das Ziel dieser Arbeit besteht in der optimalen Platzierung und dem optimalen Betrieb von Speicher- und Umwandlungstechnologien. Dafür werden in dieser Arbeit folgende Punkte berücksichtigt bzw. erarbeitet: *) Die Modellierung von Strom-, Gas- und Fernwärmenetzen wird so gestaltet, dass sie den in Österreich üblichen Strukturen entsprechen. Für das Stromnetz wird die Direct Current Load Flow (DCLF)-Berechnung (lineare LF-Berechnung) verwendet. Für die Massenströmungsnetze (Gas, Fernwärme) erfolgt die Netzdarstellung so, dass damit ebenso die (DCLF)-Methode angewandt werden kann. Die lineare Lastflussberechnung hat den Nachteil, dass Netzverluste nicht direkt berücksichtigt werden können. Dies wird in der vorliegenden Arbeit mit einer zusätzlichen Linearisierung der Verluste gelöst. *) Basierend auf statistischen Parametern wird jedem einzelnen Gebäude in der Modellregion ein Gebäudetyp (Ein-, Zwei-, Mehrfamilienhäuser, Wohnanlagen und Landwirtschaft) und ein Errichtungsjahr zugeordnet. Die verschiedenen Gebäudetypen werden in der Region so angeordnet, dass damit städtische und ländliche Gebiete repräsentiert werden (z.B. aufgrund der Leitungslängen und Lastdichten). *) Realistische Verbrauchskurven werden erreicht, indem für jedes Gebäude ein individuelles, elektrisches und thermisches Lastprofil erzeugt wird, das auf statistischen Verbrauchsparametern basiert. *) Für die Produktion wird das maximale Photovoltaik (PV)-Potential der Dachflächen und das maximale Biomassepotenzial in der Modellregion ermittelt und für die Optimierung herangezogen. Die optimale Platzierung und der optimale Betrieb der Speicher- und Umwandlungstechnologien wird mittels einjährigem Betrachtungszeitraum ermittelt. Dadurch können Langzeit- (saisonaler Ausgleich) und Kurzzeiteffekte (Tagesausgleich) gleichermaßen be- rücksichtigt werden. Für die Umsetzung der Ganzjahressimulation werden drei repräsen- tative Wochen (Sommer, Winter und Übergangszeit) generiert und in der Optimierung verwendet. Die untersuchten Szenarien sind so gestaltet, dass drei Grundfälle berücksichtigt werden: *) "technische"-Sicht: es werden nur die technischen Limitierungen betrachtet und der Speicher- und Umwandlungstechnologiebedarf aufgrund dieser Limitierungen ermittelt (z.B. thermische Leitungsgrenzströme, maximale Transformatorauslastung). *) "gesamte Region": hierbei werden zusätzlich zu den technischen Limitierungen Kosten und Erlöse für den Energieimport bzw. -export am Bilanzknoten einbezogen. *) "nachhaltige Region": dieser Grundfall ist mit jenem der "gesamten Region" vergleichbar. Einzig die Kosten für Energiebezüge sind um den Faktor 100 erhöht. Dadurch soll der gesamte Energiebezug durch die Optimierung minimiert werden, damit ein Maximum der regenerativ erzeugten Energie verwendet wird, die innerhalb der Modellregion erzeugt wird. Insgesamt werden 31 Szenarien untersucht. Diese Szenarienvariationen werden durch Abänderung verschiedener Parameter generiert. Die geänderten Parameter sind zum Beispiel: Kosten von Speichern oder Umwandlungstechnologien oder Berücksichtigung/ Variation von technischen Limitierungen (z.B. thermischer Grenzstrom von Leitungen, maximale Trafoauslastung). Szenarien, in denen Ergebnisse einen besonderen Einfluss auf das elektrische Energiesystem haben, werden hochgerechnet. Dabei werden die energetischen und leistungsmäßigen Charakteristika der Modellregion mit dem Einwohnerverhältnis (zwischen Österreich und der Modellregion) auf die Größe von Österreich skaliert und Auswirkungen auf das österreichische Elektroenergiesystem ermittelt.
de
dc.description.abstract
The strong integration of volatile, renewable, decentralized production into the electricity grid, can bring the electrical system to its limits. On the one hand, by coupling existing infrastructures (electric-, gas-, district heating-networks), relief on the electrical system can be achieved. On the other hand, a reduction in the primary energy demand for the electricity and heating demand can be realised. In addition, storages provide an effective option to balance energy and power between the volatile, renewable production and consumption. These two approaches are investigated in a region, which is modelled in a way to represent the Austrian building-, living- and energy infrastructure-characteristics. Alternatively this region is called "model region". The goal of this work is the optimal placement and optimal operation of storage and conversion technologies. Therefore in this work the following parts are taken into account or are elaborated: *) The modelling of electric-, gas- and district heating-networks will be designed in a way so that they represent commonly used structures in Austria. For the electricity grid the Direct Current Load Flow (DCLF)-calculation is used, for mass flow networks (gas, district heating), the network representation is carried out in a way so that the (DCLF) method can be applied too. The linear load flow calculation has the disadvantage in that power losses cannot be considered directly; this problem is solved in this work with an additional linearisation of the losses. *) Based on statistical parameters each individual building is assigned to a building type (single-, double-, multi-family houses, apartment buildings and agriculture) and a construction year. The different building types are located within the region in a way that the structure represents an urban and rural area (e.g. line lengths and load densities). *) Realistically load profiles are achieved by an individual, annual, electrical and thermal load profile generation for each building, these profile generations are based on statistical parameters. *) For the production, the maximum roof Photovoltaic (PV)-potential and biomass-potential in the model region is determined and used in the optimisation. The placement and operation of the storage- and conversion-technologies will be optimised for a one year period. As a result, long-term (seasonal balancing) and short-term effects (daily balancing) are considered. For the implementation of a whole year simulation, three representative weeks (summer, winter and transitional period) are generated and used in the optimisation. The investigated scenarios are designed in a way, that three basic cases are considered: *) "technical"-case: only the technical limitations are considered and the storage- and conversion technology-demands are determined according these technical limitations. *) "whole region": in addition to the technical limitations, costs and revenues for the energy import or export at the slack node are considered. *) "ecological region": this case is similar to the "whole region". Only the energy import costs are increased by a factor of 100. The aim is, that the optimisation shall minimise energy imports and maximise the usage of the renewable produce energy within the region. A total of 31 scenarios are examined. These scenario variations are generated by changing various parameters. For example, the modified parameters are: costs of storage- or conversion-technologies, or consideration/variation of technical limitations (e.g. thermal line currents, maximum transformer loads). For those scenarios where the results have an particular influence at the electrical power system, results are up-scaled. Therefore the population ratio (between Austria and the model region) is used and energetic and power characteristics of the model region are scaled to the size of Austria and the impact on the Austrian electrical power system is determined.
en
dc.language
English
-
dc.language.iso
en
-
dc.rights.uri
http://rightsstatements.org/vocab/InC/1.0/
-
dc.subject
Hybridnetz
de
dc.subject
Hybridsystem
de
dc.subject
Stromnetz
de
dc.subject
Gasnetz
de
dc.subject
Fernwärmenetz
de
dc.subject
Speicher
de
dc.subject
Umwandlungstechnologie
de
dc.subject
Optimierung
de
dc.subject
Power to Gas
de
dc.subject
HRES
en
dc.subject
Hybrid Renewable Energy System
en
dc.subject
power system
en
dc.subject
gas distribution system
en
dc.subject
thermal system
en
dc.subject
optimisation
en
dc.subject
storage
en
dc.subject
conversion technology
en
dc.subject
Power to Gas
en
dc.title
Energy storage - optimisation of the placement and operation (in a distribution grid)
en
dc.type
Thesis
en
dc.type
Hochschulschrift
de
dc.rights.license
In Copyright
en
dc.rights.license
Urheberrechtsschutz
de
dc.identifier.doi
10.34726/hss.2016.28889
-
dc.contributor.affiliation
TU Wien, Österreich
-
dc.rights.holder
Markus Heimberger
-
dc.publisher.place
Wien
-
tuw.version
vor
-
tuw.thesisinformation
Technische Universität Wien
-
tuw.publication.orgunit
E370 - Institut für Energiesysteme und Elektrische Antriebe
-
dc.type.qualificationlevel
Doctoral
-
dc.identifier.libraryid
AC12735620
-
dc.description.numberOfPages
204
-
dc.identifier.urn
urn:nbn:at:at-ubtuw:1-84229
-
dc.thesistype
Dissertation
de
dc.thesistype
Dissertation
en
dc.rights.identifier
In Copyright
en
dc.rights.identifier
Urheberrechtsschutz
de
tuw.advisor.staffStatus
staff
-
item.languageiso639-1
en
-
item.openairetype
doctoral thesis
-
item.grantfulltext
open
-
item.fulltext
with Fulltext
-
item.cerifentitytype
Publications
-
item.mimetype
application/pdf
-
item.openairecristype
http://purl.org/coar/resource_type/c_db06
-
item.openaccessfulltext
Open Access
-
crisitem.author.dept
E370 - Institut für Energiesysteme und Elektrische Antriebe
-
crisitem.author.parentorg